Hydraylic seperators
Hydraulic switcher HW 60/125
Hydraulic switcher with insulation to be connected before the distribution header.
This device allows to separate hydraulically the primary circuit from the secondary circuit so giving a greater volumetric flow in the distribution header in comparison with the flow of the boiler. It is particularly suitable to be mounted with condensing boilers.
In fact with a right setting of the boiler pump it ensures a low return water temperature (always lower than 57°C, that is the condensing temperature of the steam in the methane gas) so increasing the efficiency of the installation.
Down connection 1/2”F for the boiler sensor.
Insulation box section size: 110 x 110 mm.This device allows to separate hydraulically the primary circuit from the secondary circuit so giving a greater volumetric flow in the distribution header in comparison with the flow of the boiler. It is particularly suitable to be mounted with condensing boilers.
In fact with a right setting of the boiler pump it ensures a low return water temperature (always lower than 57°C, that is the condensing temperature of the steam in the methane gas) so increasing the efficiency of the installation.
Down connection 1/2”F for the boiler sensor.
Distributor: more circulation Boiler: less circulation |
HW 60/125 1” suitable for flow up to 2 m3/h - Code: HW60/125-04
Connection to the distribution header: 1” Male, centre distance 125 mm
Connection to the boiler: 1” Female, centre distance 250 mm
HW 60/125 1”1/4 suitable for flow up to 3 m3/h - Code: HW60/125-05
Connection to the distribution header: 1”1/4 Male, centre distance 125 mm
Connection to the boiler: 1”1/4 Female, centre distance 250 mm.
Connection to the boiler: 1” Female, centre distance 250 mm
HW 60/125 1”1/4 suitable for flow up to 3 m3/h - Code: HW60/125-05
Connection to the distribution header: 1”1/4 Male, centre distance 125 mm
Connection to the boiler: 1”1/4 Female, centre distance 250 mm.
Hydraulic switcher HW 80/125
Hydraulic switcher with insulation for power up to 165 kW, to be connected before the HV 80 distribution header. This device allows to separate hydraulically the primary circuit from the secondary circuit so giving a greater volumetric flow in the distribution header in comparison with the flow of the boiler. It is particularly suitable to be mounted with condensing boilers. In fact with a right setting of the boiler pump it ensures a low return water temperature (always lower than 57°C, that is the condensing temperature of the steam in the methane gas) so increasing the efficiency of the installation.
Maximum flow rate up to 7,25 m3/h - Max 6 bar.
Insulation box section size: 152x152 mm.
In the upper part, 1”1/4 male connection for security unit.
1/2” female connection for drain (in the lower part) and temperature sensor (located laterally).
Maximum flow rate up to 7,25 m3/h - Max 6 bar.
Insulation box section size: 152x152 mm.
In the upper part, 1”1/4 male connection for security unit.
1/2” female connection for drain (in the lower part) and temperature sensor (located laterally).
Code: HW80/570-07